7-24 Air Dispersion Modeling Report

Table 3: Modeling Input Parameters

7-24     Table 3 Modeling Input Parameters lists physical and operational details for emission sources and their stacks.  Each emission source has Stack Location coordinates provided using UTM northing and easting values (Zone 19).  However, none of the stack locations used for BPIP-Prime or AERMOD are the same as those listed on Table 3.  Please explain this discrepancy.

RESPONSE 7-24

 

The stack location coordinates are the ones used for BPIP-Prime and AERMOD.  Table 3 was not updated to reflect the stack coordinates from the most recent General Arrangement. Invenergy has determined that it will not install an AE-8 LP Fuel Gas Dew Point Heater installation at the facility.

                

RESPONDENT:

 

Michael Feinblatt, ESS Group, Inc.

 

DATE:

May 17, 2016