7-40 HRAP dated June 26, 2015

Please provide TANKS emission calculation output sheets and provide any documentation relating to size, number, and configuration of proposed diesel AST(s). Please clarify/explain.

7-40     HRAP initially stated one (1) 2MM gallon diesel fixed roof AST will be utilized.  HRA states two (2) 2MM gallon diesel AST.  Please provide TANKS emission calculation output sheets and provide any documentation relating to size, number, and configuration of proposed diesel AST(s).  Please clarify/explain.

RESPONSE 7-40

 

The current design of the facility includes two 1,000,000 gallon above-ground ULSD storage tanks.  Each tank will be approximately 80 feet in diameter and 30 feet tall.  The fugitive VOC emissions associated with the ULSD storage tanks were estimated using the TANKS program. The TANKS data printouts for the two ULSD storage tanks are attached.

 

RESPONDENT:

 

Michael Feinblatt, ESS Group, Inc.

 

DATE:

May 17, 2016